Protection Methods for Potentially Explosive Gas/Vapour Atmospheres
|
|
Protection Method
|
North America Class I
|
Europe (CENELEC)
International (IEC)
|
|
Div.
|
Standard
|
Zone
|
Standard
|
Zone
|
Standard
|
Canada (CSA)
|
US
|
Canada (CSA)
|
US
|
European Norm (EN)
|
International (IEC)
|
|
Intrinsic Safety - ia (2 faults)
|
1
|
C22.2 No. 157
|
FM3610/UL913
|
0
|
E60079-11
|
ISA 12.02.01/UL2279
|
0
|
50020
|
60079-11
|
|
Intrinsic Safety - ib (1 fault)
|
|
|
|
1
|
E60079-11
|
ISA 12.02.01/UL2279
|
1
|
50020
|
60079-11
|
|
Explosionproof Flameproof - d
|
1
|
C22.2 No. 30
|
FM3615/UL1203
|
1
|
E60079-1
|
ISA S12.22.01/UL2279
|
1
|
50018
|
60079-1
|
|
Purged Pressurized - p
|
1/2
|
CSA TIL 13A/NFPA 496
|
NFPA 496
|
1/2
|
E60079-2
|
|
1
|
50016
|
60079-2
|
|
Increased Safety - e
|
|
|
|
1
|
E79-7
|
ANSI/ISA S12.16.01/UL2279
|
1
|
50019
|
60079-7
|
|
Encapsulation - m
|
|
|
|
1
|
E79-18
|
ISA S12.23.01/UL2279
|
1
|
50028
|
60079-18
|
|
Oil immersion - o
|
|
|
|
1
|
E79-6
|
ANSI/ISA S12.26.01/UL2279
|
1
|
50015
|
60079-6
|
|
Powder filled - q
|
|
|
|
1
|
E60079-5
|
ANSI/ISA S12.25.01/UL2279
|
1
|
50017
|
60079-5
|
|
Non-incendive/non-sparking
|
2
|
C22.2 No. 213
|
FM3611/UL1604
|
|
|
|
|
|
|
|
Protection - n
|
|
|
|
2
|
E60079-15
|
UL2279
|
2
|
50021
|
60079-15
|
|
Special requirements (2 protection methods)
|
|
|
|
|
|
|
0
|
50284
|
|
|
Protection Methods for Combustible/Ignitable Dust Atmospheres
|
|
Protection Method
|
North America Class II, III
|
Europe (CENELEC)
International (IEC)
|
|
Div.
|
Standard
|
Zone
|
Standard
|
Canada (CSA)
|
US
|
European Norm (EN)
|
International (IEC)
|
|
Intrinsic Safety - ia
|
1
|
C22.2 No. 157
|
FM3610/UL913
|
|
|
|
|
Dust ignition protection
|
1
|
C22.2 No. 25 or E61241-1-1
|
UL 1203
|
20 / 21 / 22
|
EN50281-1-1
|
61241-1-1
|
|
Purged
|
1/2
|
|
NFPA 496
|
|
|
61241-4
|
|
Dust tight
|
2
|
C22.2 No. 25 or E61241-1-1
|
FM3611/UL1604
|
|
|
|
|
Non-incendive
|
2
|
|
FM3611/UL1604
|
|
|
|
|
Hazardous Locations Equipment Marking
|
|
Markings for North America
|
|
Markings for Europe
|
|
Option A: (ZoneSystem)
|
|
ATEX Directive (94/9/EC) on
|
Ex ia IIC T4 (Canada)
Class I Zone 0 AEx ia IIC T4 (U.S.)
|
|
Potentially Explosive Atmospheres
|
|
Flammable gas or vapour
|
Area classification
|
Conformity to U.S. requirements
|
Explosion protected
|
Protection method - (intrinsic safety)
|
Gas group (acetylene & hydrogen)
|
Temperature code
|
|
CE marking symbol
|
ID No. of Notified Body of the QA system
|
EU Explosive Atmospheres symbol
|
Surface (non-mining) equipment
|
Equipment category
|
Type of flammable substance
|
|
Class I
|
Zone 0
|
A
|
Ex
|
ia
|
IIC
|
T4
|
|
|
...
|
|
II
|
1
|
G
|
|
Option B: (DivisionSystem)
|
|
CENELEC (European) Directive (76/117/EEC)
|
|
Flammable gas or vapour
|
Area Classification
|
Gas group -
A: acetylene
B: hydrogen
C: ethylene
D: propane
|
Temperature Code
|
|
Conformity to CENELEC standard
|
Explosion protected
|
Protection method - (intrinsic safety)
|
Gas group (acetylene & hydrogen)
|
Temperature Class
|
EU marking for explosion protection (optional)
|
|
Class I
|
Division 1
|
Groups A, B, C, D
|
T4
|
|
EEx
|
EEx
|
ia
|
IIC
|
T4
|
|
|
ATEX Directive 94/9/EC
|
|
Equipment Group
|
Equipment Category and Level of Protection
|
Presence of Explosive Atmosphere
|
Flammable Substances
|
Correlation with Hazardous Areas
|
|
I - Mines
|
M1 - very high level of protection
|
Presence
|
Methane, Dust
|
|
|
M2 - high level of protection
|
Risk of Presence
|
|
|
II - Surface
|
1 - very high level of protection
|
Continuous Presence
|
G-Gas, Vapours Mist; D-Dust
|
Zone 0 (Gas etc.) Zone 20 (Dust)
|
|
2 - high level of protection
|
Likely to Occur
|
Zone 1 (Gas etc.) Zone 21 (Dust)
|
|
3 - normal level of protection
|
Unlikely to Occur
|
Zone 2 (Gas etc.) Zone 22 (Dust)
|
|
Ingress Protection (IP) Codes
|
|
First NUMERAL Protection Against Solid Bodies
|
SECOND NUMERAL Protection Against Water
|
|
0
|
No Protection
|
0
|
No Protection
|
|
1
|
Objects Greater Than 50 mm
|
1
|
Vertically Dripping
|
|
2
|
Objects Greater Than 12.5 mm
|
2
|
Angled Dripping (15° tilted)
|
|
3
|
Objects Greater Than 2.5 mm
|
3
|
Spraying
|
|
4
|
Objects Greater Than 1.0 mm
|
4
|
Splashing
|
|
5
|
Dust-Protected
|
5
|
Jetting
|
|
6
|
Dust-Tight
|
6
|
Powerful Jetting
|
|
|
|
7
|
Temporary Immersion
|
|
|
|
6
|
Continuous Immersion
|
|
Temperature Codes & Classes
|
|
Maximum Surface Temperature (°C)
|
US (NEC) Canada (CEC)
|
US (NEC) Canada (CEC) IEC, CENELEC
|
|
450
|
T1
|
T1
|
|
300
|
T2
|
T2
|
|
280
|
T2A
|
|
|
260
|
T2B
|
|
|
230
|
T2C
|
|
|
215
|
T2D
|
|
|
200
|
T3
|
T3
|
|
180
|
T3A
|
|
|
165
|
T3B
|
|
|
160
|
T3C
|
|
|
135
|
T4
|
T4
|
|
120
|
T4A
|
|
|
100
|
T5
|
T5
|
|
85
|
T6
|
T6
|
|
Apparatus Grouping
|
|
Typical Gas/Dust/Fibres/Flyings
|
US (NEC) Canada (CEC)
|
US (NEC) Canada (CEC) IEC, CENELEC
|
|
Acetylene
|
Class I, Group A
|
Group IIC
|
|
Hydrogen
|
Class I, Group B
|
|
Ethylene
|
Class I, Group C
|
Group IIB
|
|
Propane
|
Class I, Group D
|
Group IIA
|
|
Methane
|
Gaseous Mines*
|
Group I*
|
|
Magnesium
|
Class II, Group E
|
IEC, CENELEC do not subdivide by material types
|
|
Coal
|
Class II, Group F
|
|
Grain
|
Class II, Group G
|
|
Cotton
|
Class III
|
|
*not within scope of NEC or CEC
|
|
Class I - gas/vapour/mist, Class II - dust, Class III - fibres, flyings
|
|
Area Classifications Division vs. Zone
|
|
Type of Area
|
NEC and CEC (North America)
|
ATEX and IEC
|
|
Continuous Hazard
|
Division 1 or Zone 0
|
Zone 0
|
|
Intermittent Hazard
|
Division 1 or Zone 1
|
Zone 1
|
|
Hazard Under Abnormal Conditions
|
Division 2 or Zone 2
|
Zone 2
|
|
NEMA/CSA/UL Enclosure Types
|
|
Type
|
Application
|
Abbreviated Definition*
|
|
1
|
Indoor
|
General Purpose
|
|
2
|
Indoor
|
Protection against angled dripping water
|
|
3, 3R, 3S
|
Indoor/Outdoor
|
Protection against rain, snow
|
|
4, 4X
|
Indoor/Outdoor
|
Protection against rain, snow, hose directed water
|
|
5
|
Indoor/Outdoor
|
Protection against angled dripping water, dust, fibres, flyings
|
|
6
|
Indoor/Outdoor
|
Protection against temporary submersion
|
|
6P
|
Indoor/Outdoor
|
Protection against prolonged submersion
|
|
12, 12K
|
Indoor
|
Protection against circulating dust, fibres, flyings
|
|
13
|
Indoor
|
Protection against circulating dust, fibres, flyings, seepage
|
*refer to the enclosure standard for detailed definitions - CSA C22.2 No. 94, UL 50
|
|